Requirements For Central Station Fire Alarm Systems; Requirements For Local Protected Fire Alarm Systems; Requirements For Remote Station Protected Fire Alarm Systems; Ulc Requirements - Honeywell Silent Knight INTELLIKNIGHT 5600 Installation And Operation Manual

Addressable fire control panel
Table of Contents

Advertisement

Model 5600 Installation and Operation Manual
2.2.2
Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the 5600 sends an automatic
daily test to the central station.
3. The AC Loss Hours option must be set from 1-3 hours.
2.2.3
Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4
Requirements for Remote Station Protected Fire
Alarm Systems
1. Do not exceed the current load restrictions shown in Section 3.6.
2. The AC Loss Hours option must be set from 1-3 hours.
2.3

ULC Requirements

Install in accordance with the Canadian Electrical Code, C22.1, Part 1, Section 32.
2-4