Default Mapping For The 2 Built-In Notification Circuits - Honeywell Silent Knight INTELLIKNIGHT 5600 Installation And Operation Manual

Addressable fire control panel
Table of Contents

Advertisement

Model 5600 Installation and Operation Manual
Group
Output Point Type
OPG 1
HFS-MR, HFS-MRA, SK-Relay
OPG 2
HFS-MR, HFS-MRA, SK-Relay
OPG 3
HFS-MR, HFS-MRA, SK-Relay
OPG 4
HFS-MR, HFS-MRA, SK-Relay
OPG 5
HFS-MR, HFS-MRA, SK-Relay
OPG 6
HFS-MR, HFS-MRA, SK-Relay
OPG 7
HFS-MR, HFS-MRA, SK-Relay
OPG 8
HFS-MR, HFS-MRA, SK-Relay
OPG 9
HFS-MR, HFS-MRA, SK-Relay
OPG 10
HFS-MR, HFS-MRA, SK-Relay
OPG 11
HFS-MR, HFS-MRA, SK-Relay
OPG 12
HFS-MR, HFS-MRA, SK-Relay
OPG 13
HFS-MR, HFS-MRA, SK-Relay
OPG 14
HFS-MR, HFS-MRA, SK-Relay
OPG 15
HFS-MR, HFS-MRA, SK-Relay
OPG 16
HFS-MR, HFS-MRA, SK-Relay
OPG 17
HFS-MR, HFS-MRA, SK-Relay
OPG 18
HFS-MR, HFS-MRA, SK-Relay
OPG 19
HFS-MR, HFS-MRA, SK-Relay
OPG 20
HFS-MR, HFS-MRA, SK-Relay
OPG 21
HFS-MR, HFS-MRA, SK-Relay
OPG 22
HFS-MR, HFS-MRA, SK-Relay
OPG 23
HFS-MR, HFS-MRA, SK-Relay
OPG 24
HFS-MR, HFS-MRA, SK-Relay
Table 6-2: shows that any input SLC device with an address set within the range 1-15 will be
assigned to zone 1 as an alarm input type. An SLC output relay point assigned to address 111
or 112 will activate for an alarm in zone 1.
6.3.3
Default Mapping for the 2 built-in Notification
Circuits.
There are 2 built-in notification circuits (NAC 1 and NAC 2). They are both defaulted to
activate when any of the 5 zones are in alarm. When active, NAC 1 and NAC 2 will sound the
System Sensor synchronization pattern. To change the behavior of the default mapping of
these circuits refer to Section 6.5.
6-4
Table 6-3: Output Points
OUTPUT POINTS
Start SLC
Qty
ID
2
111
2
113
2
115
2
117
2
119
2
121
2
123
2
125
2
127
2
129
2
131
2
133
2
135
2
137
2
139
2
141
2
143
2
145
2
147
2
149
2
151
2
153
2
155
2
157
End SLC ID
Output Activates For
112
Zone 1 Alarm
114
Zone 2 Alarm
116
Zone 3 Alarm
118
Zone 4 Alarm
120
Zone 5 Alarm
122
Zone 1 Supervisory
124
Zone 2 Supervisory
126
Zone 3 Supervisory
128
Zone 4 Supervisory
130
Zone 5 Supervisory
132
Zone 1 Trouble
134
Zone 2 Trouble
136
Zone 3 Trouble
138
Zone 4 Trouble
140
Zone 5 Trouble
142
General Alarm
144
General Supervisory
146
General Zone Trouble
148
General Trouble
150
Alarm Silenced
152
Trouble Silenced
154
AC Loss
156
Resettable Aux Relay
158
Aux Door Holder
151450