Remote Station Applications; City Box Connection Using The 5220 Module - Honeywell Silent Knight INTELLIKNIGHT 5600 Installation And Operation Manual

Addressable fire control panel
Table of Contents

Advertisement

4.11 Remote Station Applications

4.11.1 City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a municipal fire alarm box or "city
box" as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service.
The city (master) box is an enclosure that contains a manually operated transmitter used to
send an alarm to the municipal communication center which houses the central operating part
of the fire alarm system.
City Box Standby Current:
Alarm Current:
Max Voltage:
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-17. This drawing also shows how
to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resis-
tor in the terminals of the NAC circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program NAC1 as auxiliary and power constant on. Program NAC2 as a non-silencing,
constant on notification circuit.
151450
Control Panel Installation
0 (Notification supervision current
accounted for in control panel draw.)
1 Amp for 1 second
24 VDC
4-21