Model 5600 Installation and Operation Manual
3.6.2
Maximum Battery Standby Load for UL 864
Table 3-4 shows the standby load calculations for the 5600 based on 24 hours of standby. The
standby load calculations of line D in the Current Draw Calculation Worksheet must be less
than the number shown in Table 3-4 for the selected battery size, standby hour and alarm time.
The numbers below have a built in 20% derating factor for the battery amp hour capacity.
Table 3-4: Maximum Battery Standby loads for 24 Hour Standby
Rechargeable
Battery Size
7 AH
226 mA
12 AH
393 mA
18 AH
593 mA
24 AH
793 mA
33 AH
1.09 A
3.6.3
Maximum Battery Standby Load for ULC
Table 3-5 shows the ULC standby load calculations for the 5600C based on 24 hours of
standby. The standby load calculations of line D in the Current Draw Calculation Worksheet
must be less than the number shown in Table 3-5 for the selected battery size, standby hour
and alarm time. The numbers below have a built in 40% derating factor for the battery amp
hour capacity.
Table 3-5: Maximum Battery Standby loads for ULC 24 Hour Standby
Rechargeable
Battery Size
7 AH
226 mA
12 AH
393 mA
18 AH
529 mA
Silent Knight does not support the use of batteries smaller than those listed in Table 3-4. If you use a battery too
small for the installation, the system could overload the battery resulting in the installation having less than the
required 24 hours standby power. Use Table 3-2 to calculate the correct battery amperes/hour rating needed for
your installation. It is recommended that you replace batteries every five years.
3-10
24 hr Standby,
5 mins. Alarm
213 mA
379 mA
579 mA
779 mA
1.08 A
24 hr Standby,
5 mins. Alarm
213 mA
379 mA
515 mA
Warning
24 hr Standby,
15 min alarm
206 mA
372 mA
572 mA
772 mA
1.07 A
24 hr Standby,
15 min alarm
206 mA
372 mA
508 mA
24 hr Standby,
20 min alarm
24 hr Standby,
20 min alarm