Battery Connection - Honeywell Silent Knight INTELLIKNIGHT 5600 Installation And Operation Manual

Addressable fire control panel
Table of Contents

Advertisement

Model 5600 Installation and Operation Manual
4.3

Battery Connection

The control panel battery charge capacity is 7.0 to 33 AH or 18 AH for ULC installations. The
main control cabinet can house batteries up to 7 AH, larger capacity batteries can be housed in
a Remote Battery Box (P/N RBB). See Section 4.3.1 for details. Use 12V batteries of the same
AH rating. Determine the correct AH rating as per your current load calculation (see Section
3.6). Maximum charging current for batteries is 3.1A @ 27 VDC.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
The following steps and diagram explain how to connect the batteries.
1. Connect the black wire from the control panel negative (–) battery terminal to the negative
(–) side of Battery #2.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2
to the (–) negative side of Battery #1.
3. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of
Battery #1.
4-6
Battery Jumper
(P/N 140694)
Shipped With Panel
Red
12V Battery
Battery 1
Figure 4-4 Battery Connection
Sup ervised
Black
12V Battery
Battery 2
Casil 7AH battery,
PN 6712
151450