AEG AS-IC01-2 Series Installation Instructions Manual page 41

Three-phase grid-tied solar inverter 12 kw to 30 kw
Hide thumbs Also See for AS-IC01-2 Series:
Table of Contents

Advertisement

40
Setting item
Run Param
PD201808 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (12-30 kW) V.2-18 EN
LCD display
Input password
0000
Run Param
UV Volt
OV time
UV time
UF Freq
OV Volt
UF time
ACUV Volt(phase volt)
184V
ACUV Time
0.20s
ACOV Volt(phase volt)
263V
ACOV Time
0.20s
ACUF Freqency
47.6Hz
ACUF Time
0.20s
ACOF Freqency
51.4Hz
ACOF Time
0.20s
Instruction
Accessing the "Run Param" interface requires a password.
You can obtain the password from your supplier if neces-
sary. Set ACUV Volt, ACUV time etc. under the related sub-
menus, press " " and " " to modify, and press "ENT" to
confirm.