20
3.2.3 Connection cables
Compatibly with the AEG inverter´s AC/DC connector specifications for different inverter models, below is an overview of the
cable specifications:
AS-IC01-12000-2 / AS-IC01-15000-2 /
AS-IC01-17000-2
AS-IC01-20000-2 / AS-IC01-25000-2 /
AS-IC01-30000-2
3.2.4 Miniature circuit breakers
In order to ensure safe operation of the inverter and circuits, it is recommender to place micro breakers or
fuses on the DC input end and on the AC output end of the inverter.
The below table reports the recommended specifications for the micro breakers:
AS-IC01-12000-2
AS-IC01-15000-2
AS-IC01-17000-2
AS-IC01-20000-2
AS-IC01-25000-2
AS-IC01-30000-2
PD201808 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (12-30 kW) V.2-18 EN
Model
The wiring shall follow local electric codes. Choose proper cables for power input and output lines.
Input and output cables shall be solar cables suitable for outdoor use.
Model
DC side
Min.cross-section
area mm² (length
≤50m) mm²
4
4
4
Table 9: Cable specifications
DC input
Recommended DC breakers
(optional for length >100m)
DC1000V, C32A, 2P
DC1000V, C32A, 2P
DC1000V, C32A, 2P
DC1000V, C40A, 2P
DC1000V, C40A, 2P
DC1000V, C50A, 2P
Table 10: Breaker specifications
AC side
Min. cross-section
Min.cross-section
area mm² (length ≤50m)
area mm²
L
(length >50m)
6
6
6
8
6
10
AC output
Recommended AC breakers
AC400V, C25A, 4P
AC400V, C32A, 4P
AC400V, C35A, 4P
AC400V, C50A, 4P
AC400V, C63A, 4P
AC400V, C63A, 4P
N/PE
4
4
6