AEG AS-IC01-2 Series Installation Instructions Manual page 40

Three-phase grid-tied solar inverter 12 kw to 30 kw
Hide thumbs Also See for AS-IC01-2 Series:
Table of Contents

Advertisement

39
Setting item
Set power
Personal
PD201808 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (12-30 kW) V.2-18 EN
LCD display
Input password
0000
set power
P-Lmt
Mode
LmtPower
P.Factor
Limit Mode
Invalid
Invalid
Auto
Manual
Limit Power
100%
Power Factor
Grid Tied Mode
Normal Mode
Power Factor 1.00
Input password
0000
Personal
MPP Start Volt
MPPT Volt
120V
Instruction
Accessing the "Set power" interface requires a password.
You can request it from your supplier if necessary.
The Set power interface of AEG inverters features 3 sub-
submenu nr. ③:
menus as below. AEG three-phase inverters only feature
① P-Lmt Mode: invalid (limited power function is invalid),
auto (special for single-phase), manual (set the limit of out-
② LmtPower: this function is only valid when the P-Lmt
put value manually);
Mode is manual, the percentage is that of the rated power
③ p.Factor: includes normal model (default value "1"), cur-
and the setting range is from 10% to 100%;
rent advanced mode and current hysteresis mode and the
setting rage is -0.9-0.99.
This function is only valid for single-phase inverters.
Accessing the "Personal" interface requires a password.
You can obtain the password from your supplier if neces-
sary. The MPPT starting voltage can be set in this menu
from 120V to 160V under the submenu of "MPPT start
volt".
39