Control - GE 339 Instruction Manual

Motor protection system/motor protection and control
Hide thumbs Also See for 339:
Table of Contents

Advertisement

SPECIFICATIONS

Control

1–14
CLOCK
Setup: ....................................................................... Date and time
IRIG-B: ...................................................................... Auto-detect (DC shift or Amplitude Modulated)
Accuracy with IRIG-B:....................................... ± 1 ms
Accuracy without IRIG-B:................................± 1 min / month
LOGIC ELEMENTS
Number of logic elements:............................. 16
Trigger source inputs per element: ............ 2 to 8
Block inputs per element: ............................... 2 to 4
Supported operations: ..................................... AND, OR, NOR, NAND, XOR, XNOR, Pickup / Dropout timers
Pickup timer: ......................................................... 0 to 60000 ms in steps of 1 ms
Dropout timer:...................................................... 0 to 60000 ms in steps of 1 ms
BREAKER CONTROL
Operation: .............................................................. Asserted Contact Input, Logic Element, Virtual Input, Manual
Function:................................................................. Opens/closes the motor breaker
START INHIBIT
Thermal Start Inhibit: ........................................ Thermal Inhibit Margin: 0 to 25 % in steps of 1%
Starts per Hour Inhibit: ..................................... Maximum: 1 to 5 starts in steps of 1
Time Between Starts Inhibit: ......................... Time Between Starts: 1 to 3600 s in steps of 1 s
Restart Inhibit: ...................................................... Restart Inhibit Delay: 1 to 50000 s in steps of 1 s
BREAKER FAILURE/WELDED CONTACTOR (50BF)
Current Supervision:.......................................... Phase Current
Current Supervision Pickup:........................... 0.05 to 20.00 x CT in steps of 0.01 x CT
Time Delay 1:........................................................ 0.03 to 1.00 s in steps of 0.01 s
Time Delay 2:........................................................ 0.00 to 1.00 s in steps of 0.01 s
Current Supervision Dropout: ....................... 97 to 98% of pickup
Current Supervision Accuracy: .................... per CT input
Timing Accuracy:................................................ 0 to 1 cycle (Timer 1, Timer 2)
Reset Time: ............................................................ <14 ms typical at 2 x pickup at 60 Hz
CT FAILURE
Inputs: ...................................................................... Neutral Current IN,
Time Delay: ........................................................... 0.00 to 60.00 s in steps of 0.01 s
3IO level accuracy: ............................................ per CT inputs
3VO level accuracy:........................................... per VT inputs
GND current level accuracy: ......................... see the specifications for phase and ground current inputs
Operate Time: ...................................................... 30 ms at 60 Hz
BREAKER TRIP COUNTER
Trip Counter Limit (Pickup):............................. 1 to 10000 in steps of 1
EMERGENCY RESTART
Function:................................................................. Defeats all motor start inhibit features, resets all trips and
Operation: .............................................................. Contact Input 1 to 10, Virtual Input 1 to 32, Logic Element 1
Daylight Saving Time
Amplitude modulated: 1 to 10 V pk-pk
DC shift: 1 to 10 V DC
Input impedance: 40 kOhm ± 10%
Command, Remote Input
<16 ms typical at 2 x pickup at 50 Hz
Neutral Current VN (from three-phase VTs)
Ground Current Ig
35 ms at 50 Hz
alarms, and discharges the thermal capacity to zero so that
a hot motor can be restarted in the event of an emergency
to 16, Remote Input 1 to 32
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL