CHAPTER 7: MAINTENANCE

Close coil

NOTE:
NOTE
NOTE:
NOTE
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Close coil monitoring is performed by a built-in voltage monitor on the Form A output
relay: #2 Close. The voltage monitor is connected across the Form A contact, and
effectively the relay detects healthy current through the circuit. To do that, an external
jumper should be made between terminals "B4", and "B5" for Close coil monitoring.
As long as the current through the Voltage Monitor is above the threshold of the trickle
currents (see Technical Specification for Form A output relays), the circuit integrity for the
Close coil is effectively normal. If the Close coil circuit gets disconnected, or if in general a
high resistance is detected in the circuitry, a Close Coil alarm will be set and the "ALARM"
and "MAINTENANCE" LEDs will be on.
The Coil Monitor feature is not available with 339 INPUT/OUTPUT option 'R'. Refer to the
Order Code section to determine if this feature is supported
Example 1: The figure below shows the connection of the breaker close coil to the relay's
close output relay for voltage monitoring of the close circuit.
To monitor the close coil circuit integrity, use the relay terminals "B4" and "A4" to connect
the Close coil, and provide a jumper between terminals "B4" and "B5" (voltage monitor).
Figure 7-7: Close Coil circuit with voltage monitoring
Output Relay 2 (CLOSE)
898792.cdr
Example 2: Some applications require that the Close Coil be monitored continuously,
regardless of the breaker position (open or closed). This can be achieved by connecting a
suitable resistor (see the table) across breaker auxiliary contact 52b in the Close circuit.
With such connections, the trickle current will be maintained by the resistor when the
breaker is closed. For these applications the setting for "BYPASS BKR STATUS" should be set
to ENABLED.
DC +
B4
A4
V
B5
52b
contact
Close
Coil
DC -
M3 BREAKER MAINTENANCE
External
jumper
7–9