CHAPTER 6: SETPOINTS

Preset statistics

339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
time the user must send a YES command to validate the RMIO. Otherwise the 339 relay
will issue a RMIO MISMATCH self-test error. It is recommended to power cycle the
339 after validating the RMIO module.
These commands can be used to preset the motor statistic data on new installations or
existing installations where new equipment has been installed.
PATH:
SETPOINTS > S1 RELAY SETUP > PRESET STATISTICS
SET MOTOR STARTS
Range: 0 to 50000 in steps of 1
Default: 0
This command presets the number of motor starts.
SET EMERG RESTARTS
Range: 0 to 50000 in steps of 1
Default: 0
This command presets the number of motor emergency restarts.
SET RUNNING HOURS
Range: 0 to 65535 in steps of 1
Default: 0
This command presets the value of motor running hours.
S1 RELAY SETUP