Control Power - GE Multilin MIGII Instruction Manual

Digital protection for electrical machines
Table of Contents

Advertisement

3.2 WIRING
CAUTION: CONTROL POWER SUPPLIED TO THE RELAY MUST MATCH THE RATED VOLTAGE OF THE RELAY. IF
Table 3–1: CONTROL POWER VOLTAGE RANGE
RANGE
LO
HI
3
3-6
THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY OCCUR.
RATED VOLTAGE
24/48 Vdc
110/250 Vdc
110/230 Vac
MIGII Digital Protection for Electrical Machines
3 HARDWARE

3.2.2 CONTROL POWER

OPERATION RANGE
19.2~57.6 Vdc
88~300 Vdc
88~264 Vac
GEK-113188A

Advertisement

Table of Contents
loading

Table of Contents