S3 PROTECTION

Time overcurrent curves

NOTE:
NOTE
6–66
The relay has phase time overcurrent protection and neutral time overcurrent protection.
The programming of these elements is identical: PKP, Inverse Curve selection, and Time
Dial Multiplier (TDM). The curve shape can be either a standard curve selected from a range
of standard ANSI, IEC, IAC curves, Definite time, or a user-defined shape programmed with
the FlexCurve™ feature. Flexcurves are also used in the thermal model; for a description of
Flexcurves, see S3 Protection/Thermal Protection.
Accurate coordination may require changing the time overcurrent characteristics of
particular elements under different conditions. For picking up a cold load, a different time-
current characteristic can be produced by increasing the pickup current value. The
following setpoints are used to program the time-current characteristics.
If the injected current is more than 20 x PKP, the trip time will be the same as 20 x PKP.
<Element_Name> PICKUP: The pickup current is the threshold current at which the
time overcurrent element starts timing. There is no intentional 'dead band' when the
current is above the pickup level. However, accuracy is only guaranteed above a 1.5
per unit pickup level. The dropout threshold is 98% of the pickup threshold. Enter the
pickup current corresponding to 1 per unit on the time overcurrent curves as a
multiple of the source CT. For example, if 100: 5 CTs are used and a pickup of 90 amps
is required for the time overcurrent element, enter "0.9 x CT".
<Element_Name> CURVE: Select the desired curve shape. If none of the standard
curve shapes is appropriate, a custom FlexCurve™ can be created by entering the trip
times at 80 different current values; see S2 SYSTEM SETUP > FLEXCURVE A. Curve
formulas are given for use with computer based coordination programs. Calculated
trip time values are only valid for I / Ipu > 1. Select the appropriate curve shape and
multiplier, thus matching the appropriate curve with the protection requirements. The
available curves are shown in the table below.
ANSI
GE TYPE IAC
Extremely Inverse
Extremely Inverse
Very Inverse
Very Inverse
Normally Inverse
Inverse
Moderately Inverse
Short Inverse
<Element_Name> MULTIPLIER: A multiplier setpoint allows shifting of the selected
base curve in the vertical time direction. Unlike the electromechanical time dial
equivalent, trip times are directly proportional to the value of the time multiplier
setpoint. For example, all trip times for a multiplier of 10 are 10 times the multiplier 1
or base curve values.
When Timed Over-Current is programmed with Definite time, the operating time is
obtained after multiplication of the selected Multiplier (TDM) by a 0.1 s base line. For
example, selection of TDM = 5 would lead to a 0.5 s operating time.
<Element_Name> RESET: Time overcurrent tripping time calculations are made with
an internal 'energy capacity' memory variable. When this variable indicates that the
energy capacity has reached 100%, a time overcurrent trip is generated. If less than
100% is accumulated in this variable and the current falls below the dropout threshold
of 97 to 99% of the pickup value, the variable must be reduced. Two methods of this
resetting operation are available, Instantaneous and Linear. The Instantaneous
selection is intended for applications with other relays, such as most static units,
which set the energy capacity directly to zero when the current falls below the reset
threshold. The Linear selection can be used where the relay must coordinate with
IEC
Curve A (BS142)
Curve B (BS142)
Curve C (BS142)
IEC Short Inverse
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
OTHER
Definite Time
TM
Flexcurve A
TM
Flexcurve B