Preparation for commissioning
1.5 Rules for wiring with DRIVE-CLiQ
● The maximum number of DRIVE-CLiQ nodes on a DRIVE-CLiQ line of the Control Unit
● The maximum number of DRIVE-CLiQ nodes on a DRIVE-CLiQ line of the Control Unit
● Examples, CU320-2 with 62.5 µs sampling time:
● Example, CU320-2 with 31.25 µs sampling time:
● If the current controller sampling time T
30
320-2 depends on the basic clock cycle of the DRIVE-CLiQ line:
– For a current controller cycle of 31.25 µs, a maximum of 3 DRIVE-CLiQ nodes are
permissible
– For a current controller cycle of 62.5 µs, a maximum of 5 DRIVE-CLiQ nodes are
permissible
– For a current controller cycle of 125 µs, a maximum of 14 DRIVE-CLiQ nodes are
permissible
– For a current controller cycle of 250 µs, a maximum of 20 DRIVE-CLiQ nodes are
permissible
– For a current controller cycle of 500 µs, a maximum of 30 DRIVE-CLiQ nodes are
permissible
310-2 depends on the basic clock cycle of the DRIVE-CLiQ line:
– From a current controller cycle of 125 µs, a maximum of 8 DRIVE-CLiQ nodes are
permissible
– Topology 1: 1 x ALM (250 µs) + 2 x servo (62.5 µs) + 2 x servo (125 µs) + 3 x TM15 +
TM54F + 4 x Safety Integrated Extended Functions with encoder SI Motion monitoring
clock cycle (p9500) = 12 ms + SI Motion actual value sensing clock cycle (p9511) = 4
ms + 4 x dir. measuring systems
– Topology 2: 1 x ALM (250 µs) + 2 x servo (62.5 µs) + 2 x U/f (500 µs) + 3 x TM15
Base 2 ms +2 x Safety Integrated Extended Functions with encoder SI Motion
monitoring clock cycle (p9500) = 12 ms + SI Motion actual value sensing clock cycle
(p9511) = 4 ms + 2 x Safety Integrated Extended Functions sensorless + 2 x dir.
measuring systems
– Topology 3: 1 x servo (62.5 μs) + 4 x U/f is not possible in connection with Safety
Integrated.
– Topology 1: 1 ALM (250 µs) on a line, 1 x servo (31.25 µs) on a line, 3 Terminal
Modules on a line and in series
– Topology 2: 1 ALM (250 µs) on a line, 1 x servo (31.25 µs) on a line, 1 direct
measuring system on a line
sampling time that does not match the other drive objects in the DRIVE-CLiQ line, the
following solutions are available:
– Insert the modified drive object into a separate DRIVE-CLiQ line.
– Modify the current controller sampling times and/or the sampling times of the
inputs/outputs of the other drive objects in the same way, so that they match the
modified sampling time again.
at one drive object has to be changed in a
i
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3