Diagnostics
3.2 Diagnostics via STARTER
Starting/stopping the ramp-function generator
Danger due to hazardous axis movement
With the corresponding ramp-function generator parameter settings (e.g. offset), the motor
can "drift" and travel to its end stop.
The movement of the drive is not monitored while the ramp-function generator is active.
Start function generator:
1. Load the function generator.
2. Select "Function generator as a commissioning tool".
3. Select an operating mode e.g. "Speed setpoint after filter".
4. Select a drive, for instance "SERVO_02".
5. Set a signal shape, for example, "Squarewave".
6. Click the "Assume control priority!" button.
7. For "Sign of life monitoring" click on the "Accept" button.
8. Click on the symbol
9. Start the function generator by clicking on the triangle next to the red zero ( "Start
10. Carefully read the "Caution" note and confirm with "Yes".
Stopping the function generator:
1. Click on the "Stop FctGen" button.
2. Click on the symbol
Parameterization
The "Function generator" parameter screen is selected with the
the STARTER commissioning tool.
276
WARNING
– Click on the symbol
or
– In the project navigator, double-click on "Drives" > "Drive_xy" > "Commissioning" >
"Function generator".
(the control priority button then changes to yellow).
FctGen" button).
The drive starts and executes the selected trace function.
Trace recordings are now possible.
Or
.
"Drive on".
"Drive off" in order to stop the drive.
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3