Siemens SINAMICS S120 Commissioning Manual page 245

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

LED
Color
Red
OPT
(OPTION)
Green
Red
RDY and DP
Red
RDY and OPT Orange
Commissioning Manual
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Status
Description, cause
Flashing
Full cyclic communication has not yet taken place.
light
Possible causes:
0.5 Hz
The controller is not transferring any setpoints.
During isochronous operation, no global
control (GC) or a faulty global control (GC) is
transferred by the controller.
"Shared Device" is selected (p8929=2) and
only one controller connected.
Flashing
Bus error,
light
incorrect parameter assignment/configuration
0.5 Hz
Flashing
Cyclic bus communication has been interrupted or
light
could not be established
2 Hz
Off
Electronics power supply is missing or outside the
permissible tolerance range.
Component is not ready.
Option board not installed or no associated drive
object has been created.
Continuous
Option board is ready.
light
Flashing
Depends on the option board used.
light
0.5 Hz
Flashing
This component has at least one fault.
light
The Option Board is not ready (e.g. after switching
2 Hz
on).
Flashing
Bus error - communication has been interrupted
light
2 Hz
Flashing
Firmware update in progress for connected Option
light
Board CBE20
0.5 Hz
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Adapt configuration between
controller and devices
Remove fault
Check power supply and/or
component
Remove the fault and
acknowledge
Remove fault