Siemens SINAMICS S120 Commissioning Manual page 167

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Add IP address for PG/PC interface in the subnet
1. Click in the toolbar on button
The "Go online" dialog opens.
2. Select the device and click "Connect" to confirm.
3. Assign an IP address to the PG/PC, which is located in the subnet of the drive.
If you have not yet done this via the Windows system control, you will be offered at this point
to temporarily assign a suitable IP address from the subnet of the drive to your PG/PC.
4. Click "Yes" to assign the IP address.
5. Confirm with "Yes".
The interface has been assigned the IP address within the PROFINET subnet.
Result
• You have assigned the PG/PC interface.
• The TIA Portal has assigned an IP address within a project.
• The online connection has been established.
Displaying and deleting temporary IP addresses
You can display and also delete all temporarily assigned addresses.
Commissioning with Startdrive
Commissioning Manual, 06/2020, 6SL3097-5AA10-0BP2
5.4 Establishing an online connection to the drive
.
Commissioning
165