Drive-Cliq Interfaces X400, X401, X402; Terminal Block -X40 External 230 V Ac Auxiliary Infeed - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130, PT1000 or PTC measuring sensor in the stator windings.
Note
Connection to terminals 1 and 2
24 VDC must be present at terminal 2 and ground at terminal 1 for operation. Pulse
suppression is activated when removed.
6.1.2.4

DRIVE-CLiQ interfaces X400, X401, X402

Table 6- 7
Connector
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
6.1.2.5

Terminal block -X40 external 230 V AC auxiliary infeed

Terminal block -X40 provides you with the option of connecting an external auxiliary infeed
(such as an uninterruptible power supply) that is independent of the main infeed. The
connection may be protected with up to a 16 A fuse.
Table 6- 8
Terminal
1
2
5
6
Max. connectable cross-section: 2.5 mm²
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
DRIVE-CLiQ interfaces X400, X401, X402
PIN
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
Terminal block X40 external 230 VAC auxiliary infeed
Designation
Technical data
L1
Factory-installed jumper to terminal 2; this jumper must be re-
moved if an external infeed is used.
L1
Connection of external 230 VAC auxiliary infeed: L1
N
Factory-installed jumper to terminal 6; this jumper must be re-
moved if an external infeed is used.
N
Connection of external 230 VAC auxiliary infeed: N
Cabinet Modules
6.1 Basic Line Connection Modules
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
147