Diagnostics

8.8 LEDs on the Voltage Sensing Module (VSM) in the Active Interface Module

8.8
LEDs on the Voltage Sensing Module (VSM) in the Active Interface
Module
Table 8- 16
Meaning of the LEDs on the Voltage Sensing Module in the Active Interface Module
LED
Color
RDY
---
(READY)
Green
Orange
Red
Green/red Flashing
Green /
orange
or
red / or-
ange
318
State
Description
Off
The electronics power supply is missing or outside the permissible tolerance range.
Steady
The component is ready for operation and cyclic DRIVE-CLiQ communication is
light
taking place.
Steady
DRIVE-CLiQ communication is being established.
light
Steady
This component has at least one fault.
light
Remark:
The LED is activated irrespective of whether the corresponding messages have been
reconfigured.
Firmware is being downloaded.
0.5 Hz
2 Hz
Firmware download is complete. Waiting for POWER ON.
flashing
light
2 Hz
Detection of the components via LED is activated (p0144).
flashing
Remark:
light
Both options depend on the LED status when module recognition is activated via
p0144 = 1.