Cable routing for signal cables to SMC10/20/30 Sensor Module
1.
2.
3.
4.
5.
6.
7.
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Route the encoder connecting cable into the cabinet from the bottom.
Remove approx. 3 cm of the insulation at the level of the shield plate in the lower part of the
cabinet and attach the cable there.
To secure the cable in accordance with EMC requirements, snap the clip onto the shield plate.
Use cable ties to secure the cable at suitable points.
Route the cable further up into the cabinet and, when it reaches the SMC10/20/30 Sensor Mod-
ule (-B81/-B82/-B83), guide it to the right to the Sensor Module. When doing so, route the cable
in a similar manner to the standard cables that have already been installed in the cabinet.
Use cable ties to secure the cable at suitable points.
Connect the cable at the encoder module SMC10/20/30 (-B81/-B82/-B83).
(→ See Chapter "Options", K46, K48 and K50 (Sensor Module Cabinet-Mounted SMC 10, 20 or
30))