Electrical installation
4.5 Connections
Cable routing for DRIVE-CLiQ connections and signal cables to the Control Unit
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Connect the signal cable at terminal block -X9.
11. Route the DRIVE-CLiQ cable through the cable bushing from the top into the Motor Module,
112
Route the DRIVE-CLiQ/signal cable to the Control Unit into the cabinet from the bottom left.
Use cable ties to secure the cable at suitable points.
Route the cable further in the cabinet to the upper side of the Control Unit. When doing so, route
the cable in a similar manner to the standard cables that have already been installed in the cabi-
net.
Use cable ties to secure the cable at suitable points.
Connect DRIVE-CLiQ/signal cable to the Control Unit.
Route the DRIVE-CLiQ/signal cable to the Motor Module from the bottom left into the cabinet.
Use cable ties to secure the cable at suitable points.
Route the cable further in the cabinet to the upper side of the Motor Module. When doing so,
route the cable in a similar manner to the standard cables that have already been installed in the
cabinet.
Use cable ties to secure the cable at suitable points.
continue to the DRIVE-CLiQ connection -X400, -X401, -X402 and connect there.
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A