Removal
The transport eyebolts can be unscrewed and removed. Depending on the length of the
cabinet or transport unit, the support rails can have a varying number of fastening screws.
These must be unscrewed and removed before the rails can be removed.
Incorrect handling of the mounting rail
The improper handling of heavy carrying rails during disassembly can cause injuries or
material damage.
• Ensure careful handling of the carrying rails during disassembly.
• Prevent screws from falling into the unit during disassembly and so causing damage
Original roof screws
Figure 3-10
After removing the crane transport aids, the transport eyebolts or the fixing screws of the
mounting rail that have been removed must be replaced by the original roof screws from the
accessories pack supplied in order to ensure compliance with the degree of protection and
proper grounding of the cabinet.
Figure 3-11
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
WARNING
during operation.
Original roof screws accessory kit
Delivery state (left), original roof screws (right)
Mechanical installation
3.3 Installing