5.4.3.3
Line/load connection
Table 5- 31
Line/load connection of the Active Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
PE1, PE2
Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1)
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Technical specifications
Voltage:
•
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
•
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frequency: 47 ... 63 Hz
Connecting thread:
•
Frame sizes FX / GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
•
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Voltage:
•
570 ... 720 V DC
•
750 ... 1035 V DC
Connections:
•
Frame sizes FX / GX: Threaded bolts M6 / 6 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
•
Frame sizes HX / JX: Connection for connection clip
Voltage:
•
570 ... 720 V DC
•
750 ... 1035 V DC
Connections:
•
Frame sizes FX / GX: Thread M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
•
Frame sizes HX / JX: d = 12 mm (M10 / 25 Nm) flat connector for busbar connection
Connecting thread:
•
Frame sizes FX / GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
•
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Line Modules
5.4 Active Line Modules
1)
1)
1)
1)
197