Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Article number
Max. connection cross-sections
- Line connection (U1, V1, W1)
- DC-link connection (DCP, DCN)
- PE connection
Max. cable length
(total of all motor cables and DC link)
- Shielded
- Unshielded
Degree of protection
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Recommended fuse
2)
- Number per phase (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
2)
Minimum current required for reliable triggering of the protective devices.
3)
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
6SL3330–
1TE34–2AA3
mm²
2 x 240
mm²
2 x 240
mm²
2 x 240
m
2600
m
3900
IP00
mm
310
mm
1164
mm
352
FB
kg
96
3NE1333-2
1
450
2
kA
4.4
3)
5.2 Basic Line Modules
1TE35–3AA3
1TE38–2AA3
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2 x 240
2600
2600
3900
3900
IP00
IP00
310
310
1164
1164
352
352
FB
FB
96
96
3NE1334-2
3NE1438-2
1
1
500
800
3
3
5.2
10
Line Modules
1TE41–2AA3
6 x 185
6 x 185
4 x 240
4000
6000
IP00
310
1653
550
GB
214
3NE1435-2
2
560
3
12.4
149