Maintenance - Siemens SINAMICS S120 Manual

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

10.3

Maintenance

Servicing involves activities and procedures for maintaining and restoring the specified
condition of the devices.
Required tools
The following tools are required for replacing components:
• Standard set of tools with screwdrivers, screw wrenches, socket wrenches, etc.
• Torque wrenches 1.5 Nm up to 100 Nm
• 600 mm extension for socket wrenches
Tightening torques for screw connections
The following tightening torques apply when tightening current-conducting connections (DC
link connections, motor connections, busbars, lugs) and other connections (ground
connections, protective conductor connections, steel threaded connections).
Table 10- 1
Note
Screw connections for protective covers
The threaded connections for the protective covers made of Makrolon may only be tightened
with 2.5 Nm.
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Tightening torques for screw connections
Thread
Ground connections, protective
conductor connections, steel
threaded connections
M3
M4
M5
M6
M8
M10
M12
M16
Aluminum threaded connections,
1.3 Nm
3 Nm
6 Nm
10 Nm
25 Nm
50 Nm
88 Nm
215 Nm
Maintenance and Servicing
10.3 Maintenance
plastic, busbars, lugs
0.8 Nm
1.8 Nm
3 Nm
6 Nm
13 Nm
25 Nm
50 Nm
115 Nm
461