Siemens SINAMICS S120 Manual page 39

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Mechanical data
Vibratory load
Transport
2)
Operation
Shock stressing
Transport
2)
Operation
Ambient conditions
Degree of protection
Protection class
Shock protection
Permissible ambient and coolant tempera-
ture (air) during operation for line-side
components, Line Modules and Motor
Modules
Permissible ambient and coolant tempera-
ture (air) during operation for Active Inter-
face Modules, Active Line Modules and
Motor Modules Chassis-2
Permissible ambient and coolant tempera-
ture (air) during operation for DC-link and
motor-side power components
Cooling method according to
EN 60146-1-1
Climatic ambient conditions
Storage
2)
Transport
2)
Operation
Environmental class / harmful chemical substances
Storage
2)
Transport
2)
Operation
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
EN 60721-3-2:1997, Class 2M2
Test values according to EN 60068-2-6 test Fc:
10 ... 58 Hz: Constant deflection = 0.075 mm
58 ... 150 Hz: Constant acceleration = 9.81 m/s² (1 g)
EN 60721-3-2:1997, Class 2M2
Test values according to EN 60068-2-27 test Ea: 98 m/s² (10 g) / 20 ms
IP00 or IP20 according to EN 60529
Class I (with protective conductor system) and class III (PELV) according to EN
61800-5-1
EN 50274 and DGUV regulation 3 when used for the intended purpose
0 ... +40 °C without derating,
>40 ... +55 °C see derating characteristics
-10 ... +45 °C for installation altitudes ≤ 1000 m above sea level without derat-
ing
-10 ... +40 °C for installation altitudes ≤ 2000 m above sea level without derat-
ing
>45 ... +60 °C for installation altitudes ≤ 2000 m above sea level, see the derat-
ing characteristics
0 ... +55 °C up to 2000 m above sea level
Active Interface Modules, Basic Line Modules, Smart Line Modules, Active
Line Modules, Motor Modules: AF
A: Air cooling
F: Forced cooling, drive unit inside the device
Line reactors, sine-wave filters, motor reactors, dv/dt filters with Voltage
Peak Limiter: AN
A: Air cooling
N: Natural cooling (convection)
Class 1K4 acc. to EN 60721-3-1:1997, temperature -25 ... +55 °C
Class 2K4 according to EN 60721-3-2:1997, temperature -40 ... +70 °C,
max. air humidity 95 % at +40 °C
better than Class 3K3 according to EN 60721-3-3:2002
Relative humidity: 5 ... 95 % (no condensation)
Oil mist, salt mist, ice formation, condensation, dripping water, spraying
water, splashing water and water jets are not permitted
Class 1C2 acc. to EN 60721-3-1:1997
Class 2C2 acc. to EN 60721-3-2:1997
Class 3C2 acc. to EN 60721-3-3:2002
System overview
3.3 Technical specifications
37