Siemens SINAMICS S120 Manual page 124

Air-cooled chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
4.7 Active Interface Modules Chassis-2
Fuses
The pre-charging input circuit components are protected against overload using fuses.
The following fuses are recommended:
• For versions with one precharging resistor for each phase, 3NE1 817-0 (50 A) fuses are
recommended.
• For versions with two precharging resistors connected in parallel for each phase,
3NE1 021-0 fuses (100 A) are recommended.
• For versions with three precharging resistors connected in parallel for each phase,
3NE1 021-0 fuses (100 A) are recommended.
Main contactor
A contactor or a circuit breaker is used as main contactor. This is used to connect the Active
Interface Modules Chassis-2 to the line supply.
The following components are recommended.
Table 4- 38
Recommended components for the main contactor
Active Interface Module
6SL3301-
7TE36-4AA0
7TE36-4AA0
7TE41-0AA0
7TE41-0AA0
7TE41-0AA0
7TE41-0AA0
7TE41-4AA0
7TE41-4AA0
7TE41-4AA0
It is only permissible that the switches are CLOSED and OPENED by the sequence control. An interlocking set 3WL9111-
1)
0BA21-0AA0, as described in Catalog LV 10, is recommended for the circuit breakers in order to exclude the risk of unin-
tentional manual operation. Manual operation bypasses the pre-charging circuit and can therefore destroy the Active
Line Module.
The main contactor is controlled via terminal -X9: HS1, HS2 of the Active Line Modules
Chassis-2. The switching capacity of the floating relay contact is described here: X9 terminal
strip (Page 227).
An additional normally open contact (NO contact) of the main contactor must be routed to
terminal -X47:3 to guarantee the feedback signal. The 24 V DC supply can be taken from
terminal strip -X42.
122
Active Line Module
Rated power
6SL3331-
7TE35-6AA0
7TE36-4AA0
7TE37-5AA0
7TE38-4AA0
7TE38-8AA0
7TE41-0AA0
7TE41-2AA0
7TE41-3AA0
7TE41-4AA0
Rated cur-
rent
355
560
400
635
450
745
500
840
560
900
630
985
710
1110
800
1260
900
1405
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
Main contactor
3RT1466-6AP36 (3 x)
3RT1466-6AP36 (3 x)
3WL1210-4CB34-4AN2-Z (Z = C22
3WL1210-4CB34-4AN2-Z (Z = C22
3WL1210-4CB34-4AN2-Z (Z = C22
3WL1212-4CB34-4AN2-Z (Z = C22
3WL1212-4CB34-4AN2-Z (Z = C22
3WL1216-4CB34-4AN2-Z (Z = C22
3WL1216-4CB34-4AN2-Z (Z = C22
Air-cooled chassis power units
)
1)
)
1)
)
1)
)
1)
)
1)
)
1)
)
1)