Line Modules
5.2 Basic Line Modules
5.2.3.3
Line/load connection
Table 5- 2
Line/load connection of the Basic Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1)
134
Technical specifications
Voltage:
•
3 AC 380 V -10% (-15% < 1 min) ... 3 AC 480 V +10%
•
3 AC 500 V -10% (-15% < 1 min) ... 3 AC 690 V +10%
Frequency: 47 ... 63 Hz
Connecting thread:
•
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
Voltage:
•
513 ... 648 VDC
•
675 ... 932 VDC
Connections:
Frame sizes FB, GB, GD: Threaded bolts M6 / 6 Nm for cable lugs according to DIN 46234 /
DIN 46235
1)
Voltage:
•
513 ... 648 VDC
•
675 ... 932 VDC
Connecting thread:
•
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
Connecting thread:
•
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
•
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
Air-cooled chassis power units
Equipment Manual, 06/2020, 6SL3097-5AE00-0BP3
1)
1)
1)
1)
1)
1)