Technical Data - Siemens SINAMICS S120 Equipment Manual

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.2.9

Technical data

Table 3- 12
Technical data for Active Interface Modules, 380 V ... 480 V 3 AC
Article number
Suitable for Active Line Module
Rated power of
Active Line Module
Rated current
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
DC link capacitance
of the drive line-up, max.
Electronics current consumption (24 V DC)
Bypass contactor
1)
Max. coolant temperature
- without derating
- with derating
Rated flow rate
for water with 70 kPa pressure drop
Sound pressure level
L
(1 m) at 50/60 Hz
pA
Frame size
Filter reactor
Article number
Cooling method
Power loss, max.
2)
- At 50 Hz 690 V
- At 60 Hz 575 V
- Dissipated to the ambient air
Liquid volumes
- Integrated reactor cooler
- Hoses supplied
Rated flow rate
for water with 70 kPa pressure drop
Coolant connections
Return and connection to filter module
Tightening torque for coolant connections
Line/load connection
U1, V1, W1 / U2, V2, W2
PE connection
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
6SL3305–
7TE41–4AA7
6SL3335-
7TE41-0AA7
kW
630
A
1405
V
3 AC 380 –10 % (-15 % < 1 min) ... 3 AC 480 +10 %
ACrms
Hz
V
DC
µF
230400
A
0.17
3WL1112-
2BB34-4AN2-Z
Z=C22
3)
°C
45
°C
50
l/min
10
dB(A)
71 / 71
JIL
6SL3005-
0DE41-4AA7
Water cooling system with integrated heat exchanger manufac-
kW
6.0
kW
6.0
kW
0.9
dm³
0.6
dm³/m
0.285
l/min
10
Nm
6
Flat connection
for M12 screw
M10 bolts
Line-side power components
3.2 Active Interface Modules
7TE41–4AA7
7TE41-4AA7
900
1405
47 ... 63 Hz
24 (20.4 ... 28.8)
230400
0.17
3WL1116-
2BB34-4AN2-Z
Z=C22
3)
45
50
10
71 / 71
JIL
0DE41-4AA7
tured out of a copper-nickel alloy
8.6
8.6
0.9
0.6
0.285
10
Pipe thread ISO 228 - G 3/4 B
(external thread 3/4", flat-sealing)
6
Flat connection
for M12 screw
M10 bolts