Siemens SINAMICS S120 Equipment Manual page 45

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Danger of an accident due to missing warning labels in the national language.
Missing warning labels in the national language can result in death or serious injury.
• Attach the component warning labels in the national language.
Risk of burns due to high surface temperature of the filter reactor
The filter reactors can become very hot. You can get seriously burnt when touching the
surface.
• Mount the filter reactors so that contact is not possible. If this is not possible, attach
• To prevent adjacent components from suffering damage due to these high
NOTICE
Material damage caused by mechanically stressed busbars and coolant connections
Mechanically stressed busbars and coolant connections can damage the device.
• Do not use the busbars and liquid coolant connections protruding from the device as
NOTICE
Damage to the device through operation of the Active Interface Module without Active Line
Module
If the Active Interface Module is operated without the associated Active Line Module, it can
be damaged.
• Only operate the Active Interface Module in conjunction with the associated Active Line
NOTICE
Damage to the Active Interface Modules when operated without coolant
If the Active Interface Module is operated without liquid coolant, even when operated under
no-load conditions, the Active Interface Module can be damaged.
• Only operate the Active Interface Module with a filled and functioning cooling circuit.
Note
Cable lengths
The connecting cables between the filter reactor and the filter module must be kept as short
as possible (max. 2 m).
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
WARNING
CAUTION
clearly visible and understandable warning notices at hazardous positions.
temperatures, maintain a ventilation clearance of at least 140 mm above the filter
reactors.
handles or as support surfaces during transport.
Module.
Line-side power components
3.2 Active Interface Modules
45