Siemens SINAMICS S120 Equipment Manual page 269

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Example of control of the coolant temperature depending on the relative humidity and the ambient
temperature
The temperature correction value delta T
maintain the temperature setpoint (T
humidity plus 4° C above the dew point.
Coolant temperature setpoint = ambient temperature + Δ TL
Table 9- 7
ΔT
depends on the humidity
L
Relative humidity [%]
[° C]
1)
Delta T
[° C]
2)
L
Temperature difference to the dew point
1)
Dew point plus 4° C
2)
If delta T
coolant temperature.
Figure 9-15
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
Cooling circuit, coolant properties and protection against condensation
20
30
40
25
18
15
-21
-14
-11
(ΔT
) is now added to the ambient temperature this provides the setpoint for the
L
L
Examples of the minimum coolant temperature setpoint depending on the humidity of 20,
30 and 40° C ambient temperature (dew point plus 4° C)
(ΔT
) is added to the ambient temperature to
L
L
) for the coolant. The value depends on the relative
set
50
60
70
12
9
7
-8
-5
-3
9.5 Examples of coolant control
80
85
90
4
3
2
0
+1
+2
95
100
1
0
+3
+4
269