Siemens SINAMICS S120 Equipment Manual page 201

Water-cooled chassis power units for common cooling circuits
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cable cross-sections
Table 7- 14
6SL3000-2DE32-6AA0
6SL3000-2DE35-0AA0
6SL3000-2DE38-4AA0
6SL3000-2DE41-4AA0
6SL3000-2DH31-0AA0
6SL3000-2DH31-5AA0
6SL3000-2DH32-2AA0
6SL3000-2DH33-3AA0
6SL3000-2DH35-8AA0
6SL3000-2DH38-1AA0
6SL3000-2DH41-3AA0
Risk of fire due to ground fault / short-circuit
Inadequate installation of the cables to the Power Module or Motor Module DC link can
result in a ground fault / short-circuit and place persons at risk as a result of the associated
smoke and fire.
• Comply with local installation regulations that enable this fault to be ruled out.
• Protect the cables from mechanical damage.
• In addition, apply one of the following measures:
Note
Maximum cable lengths
The connections should be kept as short as possible.
The maximum cable length for the specified connections is 5 m in each case.
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
Cable cross-sections for connections between the dv/dt filter plus voltage peak limiter
and Power Module or Motor Module
dv/dt filter
plus
voltage peak limiter
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Route the cables in separate cable ducts or pipes.
Connection to the DC link
(DCPS / DCNS)
[mm²]
Line voltage 3 AC 380 ... 480 V
35
70
2 x 50
2 x 120
Line voltage 3 AC 500 ... 690 V
16
16
70
70
120
2 x 70
2 x 120
Motor-side power components
7.3 dv/dt filter with Voltage Peak Limiter
Connection between dv/dt reactor and
voltage limiting network
(1U2, 1V2, 1W2) [mm²]
10
16
50
120
6
6
16
16
35
70
120
201