Advertisement

NOTICE
Damage to the dv/dt filter compact if it is not activated during commissioning
The dv/dt filter compact may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter compact during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter compact if a motor is not connected
dv/dt filters compact which are operated without a motor being connected can be damaged
or destroyed.
• Never operate a dv/dt filter compact connected to the Power Module or Motor Module
Note
Cable lengths
Keep the connecting cables to the Power Module or Motor Module as short as possible
(max. 5 m). Use an equivalent cable type when replacing the cables supplied.
7.4.3

Interface description

Figure 7-13
Water-cooled chassis power units for common cooling circuits
Manual, 08/2017, 6SL3097-4AM10-0BP0
without a connected motor.
Interface overview, dv/dt filter compact plus voltage peak limiter, type 1
Motor-side power components
7.4 dv/dt filter compact plus voltage peak limiter
215