AC Power Supply Module
Input voltage
Total Power
Outputs
Battery Charger
Diagnostic LEDs
No Load Power
Consumption
Efficiency
Inrush Current
Power Factor
Protection
Output Protection
Insulation
Dimensions
Weight
100-240 V AC, 50/60 Hz
100-240 V AC, 50/60 Hz with 12V smart battery charger
Maximum 60 W continuous; maximum 105 W peak @ 25% duty cycle
Motherboard connector (to CPU and I/O modules): 13.2 V DC ±20%, max. 4 A
AUX1A/AUX1B: 13.2 V DC ±20%, max. 8 A, on/off controlled by user
program
AUX2A/AUX2B (configurable): equal to AUX1A/AUX1B voltage, max. 8 A,
or 3.3, 5, 7.5, 9 V DC ±10%, max. 2.5A, on/off (default) controlled by user
program
Note: max. 8 A total current consumption from all outputs
12 V Lead Acid battery charger (in PS with charger)
Automatic charging of 6.5 or 10 Ah backup battery, battery temperature sensing,
overcharging protection, battery capacity test and diagnostics, automatic battery
switch-over
Status LED for: input voltage, AUX1 and AUX2 outputs, 12V Control for DO
modules, and battery
130 mA @ 220 V AC
80% typical @230 V AC, 76% typical @115 V AC (full load)
25 A maximum, for 2 mSec. Max, cold start at 25°C
0.98 typical at 230 V AC, 0.99 typical at 115 V AC
Internal line fuse, replaceable
AUX2A/B short circuit, automatic recovery on 3.3, 5, 7.5, 9 V
Input to case: 1500 V AC, input to output: 3000 V AC
56 mm W x 225 mm H x 180 mm D (2.2" W x 8.7" H x 7.1" D)
Approx. 1kg (2.2 lb)
Specifications subject to change without notice.