Note: The low limit of the DC power supply (10.8-16V) can be configured to 10.5V. The
default is 10.8V.
Common characteristics of power supply modules with battery charger:
Automatic switchover to battery on power fail
Automatic switchover to main power on power return
Temperature compensated charging
Over-charging protection
Over-discharge protection
Battery test and diagnostics, including battery controlled discharge
Battery charging current control
Characteristics of the DC power supply low-tier:
Two auxiliary voltage outputs
Short circuit protection outputs
PS located on the leftmost slot of the frame
Overvoltage protection for CPU and I/Os
Reverse voltage protection
Figure 3-1 below depicts a general view of the power supply.
Power Supply Module and Backup Battery
3-2