117 mm
82 mm
0 I/O Frame
Figure 2-2 No I/O, 2 I/O, and 3 I/O Frame Installation Dimensions and Screw Holes for
314 mm
278.5 mm
5 I/O Frame
Figure 2-3 5 I/O and 7 I/O Frame Installation Dimensions and Screw Holes for
Note: The default redundant CPU and power supply frame is the same size as the 7 I/O frame.
The following screw mount installation procedure should be used to install all ACE3600
frames (with or without a metal chassis) on a wall, except the 8 I/O (19") frame. For the 8 I/O
frame, see Installing the ACE3600 in a 19" Rack and Mounting the ACE3600 8 I/O Frame on a
Wall below.
Procedure 2-1 How to Mount the RTU Frame on a Wall
1) Drill four holes in the wall at the horizontal and vertical distances shown in Figure 2-1,
Figure 2-2, and Figure 2-3.
2) Insert M4 screws (not supplied) with head size DIN 7981C/ST4, 2x38mm into the holes.
3) Remove the modules from the frame.
4) Lift the RTU frame and hang over the four screws.
5) Remove the outermost modules in order to access the screws.
195 mm
161 mm
2 I/O Frame
Installation
7 I/O Large (or Redundant) Frame
Installation
2-3
Installation
234 mm
199.6 mm
3 I/O Frame
391 mm
356.9 mm