Safety Tests; Environmental Tests - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

Chapter 17 – Technical Specifications
2.12

Safety Tests

2.13

Environmental tests

RPV311-TM-EN-7
Safety
IEC 60255-5
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-14
IEC 60255-21-1
Vertical Axis:
Frequency Range: 1Hz – 35Hz
Cross-over Frequency: 8.42Hz
Severity: 3.5mm zero-peak displacement
below 8.14Hz
1g zero-peak acceleration above 8.14Hz
Sweep Rate: 1 Octave/minute
Number of Sweep Cycles: 1
Configuration: Operational throughout
Safety tests
IEC 61010-1
Inpulse – 5KV
Dielectric withstand – 3,3KVDC for 60
seconds
Insulation > 100M Ω
Environmental tests
-40°C, 16 hours (Cold)
+85°C, 16 hours (Dry heat)
95% no condensation, 55°C (Damp heat)
-40°C to 85ºC / 9 hours / 2 cycles (Change
of temperature)
Class 2 (Vibration)
RPV311
273