Earth Connection; Figure 108: Rpv311 Grounding - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
8.1.2
RA331, RA332 and RA333
9

Earth Connection

9.1.1
RA33x Earthing
RPV311-TM-EN-7
If the module does not work as described, carefully check all power and signal
connections. Refer to Chapter 16: Maintenance and Troubleshooting for
troubleshooting guide;
To turn off the module, switch off the external switch or circuit breaker. All indicators
will be off.
Do not operate the module without the safety ground connection in place;
Connect power cable (including safety grounding) to the module. The Mains indicator
on the front and back panel will light immediately;
A self-test will be executed and the Ready indicators on the front and back panels will
light up when the process has ended;
If a pair of fiber-optics have already been connected to the processing unit, the Link
indicator will light up, indicating that there is a communication between the modules;
If the module does not work as described, carefully check all power and signal
connections. Refer to Chapter 16: Maintenance and Troubleshooting for
troubleshooting guide;
To turn off the module, switch off the external switch or circuit breaker. All indicators
on the front and the back panels will be off.
To ensure proper operation of the equipment under adverse conditions of
electromagnetic compatibility, connect the equipment protective earth terminal to
the panel using a copper strap of at least 10 mm wide with M6 ring lug. As shown in
the Figure 108.

Figure 108: RPV311 Grounding

To ensure proper operation of the equipment under adverse conditions of
electromagnetic compatibility, connect the equipment protective earth terminal to
Chapter 15 – Installation
220