Safety Tests; Environmental Tests - GE DR60 Technical Manual

Table of Contents

Advertisement

1.14

Safety Tests

1.15

Environmental tests

DR60-TM-EN-2A
Safety
IEC 60255-27:2014
IEC 60255-5
Inpulse - 5KV
Dielectric withstand - 3,3KVDC for 60 seconds
Insulation > 100M Ω
Cold
IEC 60068-2-
1
Dry heat
IEC 60068-2-
2
Damp heat
IEC 60068-2-
30
Change of
IEC 60068-2-
temperature
14
Vibration
IEC 60255-
21-1
Conducted emission
0,15 MHz to 0,50 MHz
79 dB(µV) quasi peak
66 dB(µV) average
0,5 MHz to 30 MHz
73 dB(µV) quasi peak
60 dB(µV) average
Safety tests
Environmental tests
-40°C, 16 hours
+55°C, 16 hours
95% no condensation, 55°C (Damp heat)
-40°C to 55ºC / 9 hours / 2 cycles
Class 2
DR60
Class A
116