GE RPV311 Technical Manual page 232

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
RPV311-TM-EN-7
3-element (Phases A, C and
neutral) connection: in this case,
the fourth element is derived of
the values measured by the other
elements. The three elements are
equivalent to the values applied
to the equipment.
3-element (Phases B, C and
neutral) connection: in this case,
the fourth element is derived of
the values measured by the other
elements. The three elements are
equivalent to the values applied
to the equipment.
2-element connection: in this
case, the neutral voltage is zero,
and the three phase-to-ground
voltage are computed based on
the
two
line-to-line
applied to the equipment
In circuits of 1 element, the measurements can be in two different ways:
An isolated phase or neutral measurement: If the element is a phase, only the current
related to this channel is measured considering the off-set compensation. If the
element is a neutral, the current related to this channel is measured without the off-
set compensation.
A 3-Phase synthesis: The magnitude for the 3-phases is considered with the same
value as that of the channel measured and balanced (i.e., angles with 120º between
each other).
voltages
Chapter 15 – Installation
232