Panasonic Electric Works Nordic AB
MEW01091
25.7
Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B7.
"A"
"A"
Depending on the
chosen type, 0, 1, 2 or 3
the following will be
shown:
Rev: 3
Re-enable output (H2/B7)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8)
will be turned OFF, if there are no other disablements.
When all outputs type Alarm devices have been re-enabled, the LED
"Fault / Disablements Alarm devices" (L13) will be turned OFF.
Text in display
Disable or re-enable
Disable zone
Re-enable output
Re-enable output: 0
0=Loop unit 1=S 2=R0 3=EXPB
Re-enable technical address 000 output 0
Re-enable S0
Re-enable R0
Re-enable expansion board 0 output 0
81
Expansion board (EXPB) 0-7.
Relay output 0-7 (4581) alt. Output 0-2 (4583).
EBL128 Operating Instructions V1.1.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B7
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
88
Comments
According to chapter
"Access", see page 78.
Press:
"0"=MIO (3361) or
ASI (3377) or
ASB (3378) or
AOU (3364)
"1"=C.i.e. output S0-S1
"2"=C.i.e. output R0
"3"=C.i.e. exp. board
output.
Press "A" to accept.
If there are no outputs to
L
re-enable, menu B7 will be
shown again.
L
L=a list in which you can
scroll. Regarding the ASI
(3377) & ASB (3378) unit
L
outputs:
0=high priority
L
1=low priority
If it's the correct output to
re-enable, press "A" to
accept. If not, scroll or
write the wanted output
and press "A" to accept.