Finishing The Transmitter Connection (Wall Mount) - Siemens SITRANS FS130 Compact Operating Instructions

Ultrasonic flowmeters
Table of Contents

Advertisement

Connecting
4.7 Connecting wall mount enclosure
5. Connect ground to terminal
below at right using a screwdriver.
Note
The terminal connector is detachable
For easier access unplug the terminal connector. After connecting the wires, plug the
terminal connector back in.
6. Tighten cable gland.
7. Mount power supply protection cover and fasten protection cover screw.
4.7.9

Finishing the transmitter connection (wall mount)

Connection check-up
1. Check individual wire installation by tugging firmly.
2. In case of Ex, remove all plastic blind plug caps and mount Ex rated cable glands or Ex rated
blind plugs in unused cable entries.
To ensure IP rating, remove caps and mount appropriate cable glands and blind plugs in
unused cable entries.
Firmly tighten cable glands.
82
L/+
N/-
Protective Earth (PE)
AC connection
Power: 100 to 240 V AC, 47 to 63 Hz
and power to terminals L/+ and N/- in the manner shown
 
Compact Operating Instructions, 12/2023, A5E38755607-AF
DC connection
 
Power: 20 to 27 V DC
SITRANS FS130 & FS230