Connecting
4.6 Connecting industrial enclosure
5. Connect wires to terminals using wiring tool.
– Industrial enclosure:
6. Tighten cable gland.
Note
For Ex versions active or passive current output is preselected at ordering and cannot be
changed.
Non-Ex versions can be connected as either active or passive.
Note
Load
Signal output: < 500 Ω at 14 to 24 VDC (active), 14 to 30 VDC (passive)
Relay output: 30 VAC/VDC, 100 mA
Passive signal input: 15 to 30 VDC, 2 to 15 mA
62
5
4
Active current output
Functional Earth
Active current output
 
Cp-
C
Ca+
+
-
 
C
Ca+
Passive current output
U
0
Compact Operating Instructions, 12/2023, A5E38755607-AF
6
5
Passive current output
Functional Earth
 
Cp-
U
0
C
Ca+
 