Connecting
4.7 Connecting wall mount enclosure
Connect wires
Note
Additional load resistor
Depending on the internal load of an externally connected device, an additional load resistor
might be required, for the pulse, status and frequency functions to work properly. See Technical
specifications (Page 97) for load specifications.
1. Remove cap and ferrule from cable gland and slide onto cable.
Wall mount enclosure: Remove blind plug and fit cable gland.
2. Push cable through open gland and cable path.
3. Restore ferrule and tighten cap to hold cable in place.
In case of shielded cables, use metal cable glands for proper connection.
4. Connect wires to terminals using a screwdriver.
Note
The terminal connector is detachable
For easier access unplug the terminal connector. After connecting the wires, plug the
terminal connector back in.
5. Tighten cable gland.
The numbers in the graphics below refer to table Preparing wall mount enclosure
connections (Page 66)
If connected as input or output (channels 2 to 4)
Termination example for channel 3
76
Active configuration
-
+
Passive configuration
Compact Operating Instructions, 12/2023, A5E38755607-AF
-
+