Setting Communications Parameters (Modbus Tcp Protocol) - Huawei NetCol8000-C190 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C190:
Table of Contents

Advertisement

NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
Table 4-7 Baud rate and communication address settings
Parameter
Baud rate
Communic
ation
address
RS485
monitoring
grouping
----End

4.5.4.3 Setting Communications Parameters (Modbus TCP Protocol)

Context
This section applies to the scenario where the device is connected to the NMS.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > WAN IP Settings, and
set the IP address, subnet mask, and gateway based on the actual plan.
Figure 4-8 WAN IP Settings
Step 2 On the home screen, choose Settings > Comm Settings > Modbus Settings and
set Link mode to Server and client or Client. Set Client encryption to Enable.
Issue 02 (2022-03-30)
Setting
9600, 19200
1–255
Enable,
Disable
NO TE
The WAN IP address cannot be in the 192.168.X.X network segment.
Copyright © Huawei Technologies Co., Ltd.
Setting Method
Set the baud rate as required. The value should be
consistent with that set on the NMS.
Set the communication address of the smart
cooling product as planned. The NMS
communicates with the smart cooling product
through this address, and the communication
addresses of two smart cooling products
connecting to the same NMS must be unique.
● For scenarios without grouping, set this
parameter to Enable for the last device.
● For scenarios with grouping, set this parameter
to Enable for the last device in each teamwork
control group.
4 Power-On Commissioning
86

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c190d40edNetcol8000-c190d40ec

Table of Contents