Installing Fan Cables - Huawei NetCol8000-C190 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C190:
Table of Contents

Advertisement

NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
PIN
16
17
18
Procedure
Step 1 Determine the cable end for the corresponding components based on the
information about the signal cable terminal block. Ensure that the cable length is
sufficient for crimping and slack is ensured.
Step 2 Identify the positive and negative terminals of power and signal cables based on
the cable labels. Crimp the terminals from left to right based on the terminal
definitions.
Step 3 Check them after the crimping is complete.
----End

3.6.5 Installing Fan Cables

Context
Cables inside the heat exchanger module and fan module have been connected
before delivery. You only need to connect the interconnection terminals of the fan
power cables, signal cable, and NTC cable onsite.
Procedure
Step 1 Determine the cable route.
Issue 02 (2022-03-30)
Definition and Function
Copyright © Huawei Technologies Co., Ltd.
3 Installation
52

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c190d40edNetcol8000-c190d40ec

Table of Contents