NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
(4) Heat exchanger
(7) Chilled water outlet pipe
(10) PICV valve

3.1.3 System Requirements

Pipe Ports
Table 3-1 Pipe ports
Item
Water outlet pipe
Water inlet pipe
Drainpipe
Installation Requirements
Table 3-2 Installation requirements
Item
Door
Floor
Pipe routing
Maintenance clearance
Power distribution
requirements

3.2 Installation Preparations

3.2.1 Tools

Table
NetCol8000-C. Add or delete tools as required.
Issue 02 (2022-03-30)
3-3,
Table
3-4,
Table 3-5
Copyright © Huawei Technologies Co., Ltd.
(5) Chilled water inlet pipe
(8) Needle valve
(11) Chilled water outlet pipe
connector
Specifications
G 2 inch port with external threads
G 2 inch port with external threads
G 1 inch port with external threads
Specifications
Width ≥ 1.3 m, height ≥ 2.3 m
Floor bearing capacity ≥ 400 kg/m
height ≥ 700 mm
Left or right pipe routing
Front maintenance clearance ≥ 900 mm
Leakage circuit breakers are not recommended
for the active power supply route. If a leakage
circuit breaker is required by the customer or
local regulations, select the residual current
circuit breaker (RCCB) that is insensitive to
single-phase DC pulsation and transient
impulse current.
and
Table 3-6
list the tools for installing the
3 Installation
(6) Drainage valve
(9) Outlet water thermometer
2
; floor
26