Monthly Maintenance - Huawei NetCol8000-C190 User Manual

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C190:
Table of Contents

Advertisement

NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)

6.1.1 Monthly Maintenance

This section describes routine maintenance items for an indoor unit. Record
maintenance results in the table after a maintenance item is complete.
Table 6-1 Monthly maintenance
Maintenan
ce Item
Air filter
Indoor fan
Condensate
drip pan
PICV valve
Issue 02 (2022-03-30)
Exercise caution during professional maintenance. For details, contact
technical support.
When replacing a component, do not lean the component against the
cabinet.
Operation
Check that the air filter is
clean and not blocked.
Check that the air filter is
not damaged or distorted.
Check that the indoor fan
guard is not misshapen.
Check that the indoor fan
blades are intact.
Check that no foreign
matter exists in the fan.
Check that the indoor fan
generates no abnormal
sound during operation,
such as metal friction sound
and harsh noises.
Check that the screws on
the indoor fan are not loose
or distorted.
Check that the condensate
drip pan is not dirty or
blocked.
Check that cables are
securely connected to the
chilled water valve and its
actuator.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
Clean the air filter.
Replace the air filter
(recommended interval: every six
months).
Repair or replace the fan guard if it
is misshapen.
Replace the fan.
Clear foreign matter.
Clear foreign matter and check
that screws securing the fan are
tightened.
Tighten or replace the screws.
Clean the drip pan.
Secure the cables connected to the
chilled water valve and its actuator.
6 Maintenance
107

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c190d40edNetcol8000-c190d40ec

Table of Contents