Software Specifications - Mitsubishi Electric MELSEC iQ-R Series User Manual

Interface module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Software specifications

The following table shows the specifications of MX MESInterface-R.
Item
Description
Basic operation specification
Specification for the operation (job), startup condition for the job (trigger condition),
operation unit of a job (action), and network information.
Device memory input/output
Specification for the accessible target device types and access units (device tags).
specification
DB input/output specification
Specification for the accessible databases, access units (access table/procedure,
access field/procedure argument), and buffering of output data (DB buffering) at the
time of disconnection.
Variable input/output
Specification for freely definable user variables (local variables, global variables),
specification
system variables for browsing system information, and data types of variables.
Data operation and processing
Specification for the operation processing such as addition and subtraction.
specification
External communication client
Specification for the communication from an MES interface module to external
devices.
Security
Specification for security.
Basic operation specification
Item
Job (number of
Maximum
settings)
Action (number of
Maximum
settings)
For one job
Trigger condition
For one job
Configuration type
Event/condition type
Condition combination
type
Trigger buffering count
Time information
Time
handling (time
Daylight saving time
*2
information)
Time zone
Ethernet
Connection method
Number of channels
Number of default
gateways
MES Interface
Number of tools that
Function Configuration
can be connected
Tool
simultaneously
*1 Up to five actions can be set when using a DB communication action with "Multiple Insert" selected.
*2 When using the daylight saving time function of a CPU module for an RD81MES96, use an RD81MES96 with firmware version '03' or
later. If using one with firmware version '02' or earlier, it may cause malfunction due to the time information difference with the CPU
module.
For information on the firmware version of a CPU module, refer to the manual of a CPU module used.
Specification
RD81MES96N
64 jobs
1920 actions
30 actions
*1
• Main processing: 20 actions
• Pre/post-processing: 10 actions
2 events/conditions
• Single event
• Multiple events
• Condition combination event
• Precondition  Event
• Single handshake
• Multiple handshake
• Condition (value monitoring)
• Condition (period of time)
• Event (value changed)
• Event (fixed time)
• Event (fixed cycle) (timer interval/time interval)
• Event (module monitoring) (MES interface module/control CPU)
• OR combination
• AND combination
192 times (A value is cleared due to power interruption/reset/setting update.)
Acquired from a CPU module (CPU No.1 in a multiple CPU system).
IPv4
2 channels (CH1/CH2) (Note that they cannot be connected to a same network, and no routing function
between CH1 and CH2.)
1 (It can be registered only in CH1 or CH2.)
5 (Maximum number of connections to a single MES interface module)
Reference
Page 19 Basic operation
specification
Page 20 Device memory input/output
Page 21 DB input/output
Page 23 Variable input/output
Page 23 Data operation and
processing
Page 23 External communication
client
Page 23 Security
RD81MES96
30 actions
• Main processing: 20 actions
• Pre/post-processing: 10 actions
• Single event
• Multiple events
• Condition combination event
• Precondition  Event
• Single handshake
2 SPECIFICATIONS
2.1 Performance Specifications
2
19

Advertisement

Table of Contents
loading