5.4 CONFIGURATIONS MENU

5.4 CONFIGURATIONS MENU
MOTOR: Collr-Ring
ENTER to modify
FUNCTION:
The type of motor is selected here. Different setpoints are used for the two different motors and operation of
the relay is altered. This configuration setpoint must be entered correctly.
LINE FREQ: 60 Hz
ENTER to modify
FUNCTION:
Enter line frequency here for system.
PF REF: Internal
ENTER to modify
5
FUNCTION:
Enter the source for the voltage reference for power factor calculations. See Section 2.4, Electrical installation
for proper wiring details.

RTU ADDRESS: 1

ENTER to modify
FUNCTION:
Enter the Modbus slave address here which must be unique to all SPMs on the same communication link.
BAUD RATE: 19.2k
ENTER to modify
FUNCTION:
This setpoint allows the user to select the desired baud rate.
PARITY: None
ENTER to modify
FUNCTION:
Enter the type of parity necessary.
5-
12
Courtesy of store.ips.us
Range: Collr-Ring, Brushless
Range: 50 Hz, 60 Hz
Range: Internal, External
Range: 1 to 254
Step: 1
Range: 300, 600, 2400, 4800, 9600, 19.2k, 38.4k, 57.6k, 115k
Range: None, Odd, Even
SPM Synchronous Motor Protection and Control
5 SETPOINTS

5.4.1 MOTOR TYPE

5.4.2 LINE FREQUENCY

5.4.3 POWER FACTOR REFERENCE

5.4.4 RTU ADDRESS

5.4.5 BAUD RATE

5.4.6 PARITY